تم إنشاء هذا النص العربي تلقائيًا ولم تتم مراجعته من قِبل شخص. وهو ليس النص الرسمي. في حال وجود أي اختلاف، يسود النص الأصلي. عرض النص الأصلي (الإنجليزية) ←
ADOSH-SF Code of Practice CoP 28.0 - Hot Work Operations (e.g. Welding and Cutting)
Abu Dhabi Occupational Safety and
Health System Framework
(ADOSH-SF)
Code of Practice
CoP 28.0 – Hot Work Operations
(e.g. Welding and Cutting)
Version 4.1
February 2026
ADOSH-SF – Codes of Practice
CoP 28.0 - Hot Work Operations (e.g., Welding and Cutting)
Version 4.1 – 16h February 2026
Page 2 of 16
Table of Contents
1. Introduction ................................................................................................................................... 3
2. Training and Competency .............................................................................................................. 4
3. Requirements ................................................................................................................................. 5
3.1 Roles and Responsibilities ....................................................................................................... 5
3.2 Planning and Assessment........................................................................................................ 6
3.3 Hot Work ................................................................................................................................. 7
3.4 Hazardous Areas ..................................................................................................................... 9
3.5 Electric Arc Welding .............................................................................................................. 10
3.6 Gas Welding .......................................................................................................................... 10
3.7 Gas Cylinders ......................................................................................................................... 11
3.8 Inspection.............................................................................................................................. 13
4. Document Amendment Record ................................................................................................... 14
ADOSH-SF – Codes of Practice
CoP 28.0 - Hot Work Operations (e.g., Welding and Cutting)
Version 4.1 – 16h February 2026
Page 3 of 16
1. Introduction
(a) This Code of Practice (CoP) applies to all employers within the Emirate of Abu Dhabi.
This CoP is designed to incorporate requirements set by Abu Dhabi Public Health
Centre and Sector Regulatory Authorities in the Emirate of Abu Dhabi.
(b) This CoP establishes the requirements and standards so that the risks associated with
hot work operations are assessed, that control measures are implemented in
accordance with the hierarchy of controls and that control measures are taken to
prevent injury, illness and disease to persons who might be exposed to risks arising
from those activities.
(c) This CoP specifies precautions to be taken prior to and during hot work (including
welding and cutting), to prevent the possibility of fire or explosion, which may result
in harm to persons or property. In particular, such precautions apply to hot work during
manufacturing, construction, maintenance, repairs, demolition and where plant or
equipment contains flammable, combustible or explosive material.
(d) ‘Hot Work” is a general term referring to grinding, welding, thermal or oxygen cutting
or heating, and other related heat-producing or spark-producing operations.
(e) ‘Welding” has been defined as the fusion of two pieces of metal, rendered plastic or
liquid by heat or by pressure, or by both. There are many different welding processes,
but the two most commonly used in the construction industry are gas welding and
electric arc welding.
(f) ‘Hazardous Area” has been defined as an area in which flammable liquids, vapours or
gases, combustible liquids, dusts or fibres, or other flammable or explosive substances
may be present.
ADOSH-SF – Codes of Practice
CoP 28.0 - Hot Work Operations (e.g., Welding and Cutting)
Version 4.1 – 16h February 2026
Page 4 of 16
2. Training and Competency
(a) Employers shall ensure that OSH training complies with the requirements of:
(i)
ADOSH-SF – Element 5 – Training, Awareness and Competency;
(ii)
ADOSH-SF – Mechanism 7.0 – Occupational Safety and Health Practitioner and
Service Provider Registration.
(b) In accordance with
ADOSH-SF – Element 1 – Roles, Responsibilities and Self-Regulation
Section 3.2.5 employers shall ensure employees required to implement the
requirements of this CoP are trained in hot work operations (welding and cutting), and
understand the risks associated with using the equipment and the control measures
put in place by employers.
(c) Training for employees shall be competency-based and include:
(i) systems of work needed for the safe hot work operations;
(ii) types and selection of correct welding and cutting equipment;
(iii) type, selection and use of PPE; and
(iv) care, maintenance and inspection of welding and cutting equipment.
(d) Employers shall conduct additional retraining whenever a periodic inspection reveals,
or there is reason to believe, that there are deviations from or inadequacies in the
employee’s knowledge of the correct hot work operations.
(e) Employers shall maintain a record of the required training that contains the following
information:
(i) name and ID number;
(ii) Emirates ID number;
(iii) subject(s) of training;
(iv) date(s) of training; and
(v) person(s) providing the training.
ADOSH-SF – Codes of Practice
CoP 28.0 - Hot Work Operations (e.g., Welding and Cutting)
Version 4.1 – 16h February 2026
Page 5 of 16
3. Requirements
3.1 Roles and Responsibilities
3.1.1 Employers
(a) Employers shall undertake their roles and responsibilities in accordance with the
general requirements of
ADOSH-SF – Element 1 – Roles, Responsibilities and Self-
Regulation Section 3.2.5.
(b) Employers shall undertake their specific roles and responsibilities in accordance with
the following:
(i) hot works plant and equipment (eg. welding and cutting equipment) shall be
appropriate for the task and maintained in good working condition;
(ii) all work involving the use of hot works plant and equipment is appropriately
planned, organized and appropriately supervised;
(iii) those involved in use of hot works equipment are trained and competent;
(iv) all hot works equipment is inspected on a daily basis by a competent person;
(v) implement an appropriate medical surveillance program in accordance with
ADOSH-SF – CoP 5.0 – Occupational Health Screening and Medical Surveillance;
(vi) conduct appropriate occupational air monitoring in accordance with
ADOSH-SF –
Element 7 – Monitoring, Investigation and Reporting and take the appropriate
actions to reduce exposures to employees working in the area and monitor their
health; and
(vii) employees using hot works equipment are provided with the particular personal
protective equipment necessary to protect them from the hazards in accordance
with the requirements of
ADOSH-SF – CoP 2.0 – Personal Protective Equipment.
For example, appropriate protective clothing for welders may include: a shield or
helmet with a filtered lens; fire resistant gloves; a leather apron; boots; leather
spats; a felt skull-cap or beret and preferably overalls.
3.1.2 Employees
(a) Employees shall undertake their roles and responsibilities in accordance with the
general requirements of
ADOSH-SF – Element 1 – Roles, Responsibilities and Self-
Regulation Section 3.2.7.
(b) Employees shall undertake their specific roles and responsibilities in accordance with
the following:
(i) employees shall inspect work equipment before use, report any activity or defect
relating to the equipment which they believe is reasonably foreseeable to
endanger their safety or the safety of another person; and
(ii) employees shall use safety devices provided to use with the welding and cutting
equipment by employers in accordance with training or instruction received in the
use of the work equipment or other device.
ADOSH-SF – Codes of Practice
CoP 28.0 - Hot Work Operations (e.g., Welding and Cutting)
Version 4.1 – 16h February 2026
Page 6 of 16
3.2 Planning and Assessment
(a) Employers shall ensure that no hot works are allowed to be undertaken, outside of a
designated area, unless a specific Hot Work Permit to Work is in place.
(b) The Hot Work Permit to Work shall be in line with the requirements of
OSHAD-SF – CoP
21.0 – Permit to Work Systems.
(c) Employers shall evaluate each site or operation to determine if hazards are present
and the hot works equipment shall be assessed using risk management practices as
required by
ADOSH-SF – Element 2 – Risk Management.
(d) Employers shall ensure the following:
(i) assessment of the various risks and establishment of systems of work which are
safe to both contractors and the public;
(ii) that effective procedures and control measures are in place which are implemented
in order to manage the hot work operations;
(iii) that for the Building and Construction Sector the management of hot work
requirements are included in the Pre-Tender Safety and Health Plan in accordance
with
ADOSH-SF – CoP 53.0 – OSH Management During Construction Work; and
(iv) that associated safe systems of work, and site rules are included in the Safety and
Health Construction Management Plan (OSH -CMP) in the case of the Building and
Construction Sector in accordance with
ADOSH-SF – CoP 53.0 – OSH Management
During Construction Work.
(e) When assessing the various risks employers shall consider if there are specific hot
work-related hazards such as:
(i) fire and explosion;
(ii) burns;
(iii) fumes, gases and ventilation;
(iv) electricity; and
(v) radiation.
ADOSH-SF – Codes of Practice
CoP 28.0 - Hot Work Operations (e.g., Welding and Cutting)
Version 4.1 – 16h February 2026
Page 7 of 16
3.3 Hot Work
3.3.1 General Requirements
(a) Employers shall ensure the following:
(i) material safety data sheets for electrodes, fluxes and coatings are made available
to employees required to perform welding activities;
(ii) the protection of welders and other persons in the vicinity of the work from burns
caused by sparks, hot metal, etc.;
(iii) the erection of screens for the protection of persons in the vicinity of the welding
work from harmful radiation rays produced by the process;
(iv) the use of welding booths, where reasonably practicable;
(v) gas systems (eg. cylinders, regulators, hoses, etc) are in good working order;
(vi) all welding-associated waste is placed in a hot waste crate located as close as
reasonably practicable to where the welding activities are carried out. Such hot
waste includes slag, shot crucibles and metal off-cuts; and
(vii) in areas where welding work is performed, competent First Aiders with relevant
experience. This shall include, but is not limited to:
1. persons overcome by welding fumes or gases;
2. burns; and
3. “welding flash” eye injuries.
3.3.2 Designated Hot Work Area(s)
(a) A designated hot work area is a permanent location designed for hot work. These
areas do not normally require a permit to perform hot work.
(b) Where it is reasonably practicable to do so, employers shall ensure that all hot works
are undertaken within a designated hot works area.
(c) Access / Egress to the designated area shall be restricted for non-authorized
person(s).
(d) A designated hot work area shall be:
(i) of non-combustible, fire-resistive construction, essentially free of combustibles
and flammables;
(ii) appropriately segregated from adjacent areas;
(iii) equipped with automatic fire protection or fire extinguishers;
(iv) inspected and approved by management; and
(v) have appropriate ventilation.
ADOSH-SF – Codes of Practice
CoP 28.0 - Hot Work Operations (e.g., Welding and Cutting)
Version 4.1 – 16h February 2026
Page 8 of 16
3.3.3 Fumes and Gases
(a) Employers shall ensure the following:
(i) appropriate control measures are utilized to reduce as far as reasonably
practicable, the exposure level of personnel to harmful fumes and gases. These
control measures include but are not limited to:
1. removal of rust inhibitors, paints, degreasers and other coatings prior to
welding;
2. segregation of degreasing operations from welding tasks; and
3. positioning of welders away from welding fumes.
(ii) employees required to perform welding work are monitored for any adverse side
effects on their health, related to exposure to welding fumes and gases, as per the
requirements of
ADOSH-SF – CoP 5.0 – Medical Surveillance;
(iii) appropriate ventilation is provided in all locations where welding work is carried
out which may consist of:
1. general ventilation;
2. dilution ventilation (e.g. diluting the concentration of contaminants in the
atmosphere with fresh air); or
3. local exhaust ventilation (LEV).
(iv) the determination of the type of ventilation to be used takes into consideration
that, in most instances, general or dilution ventilation by themselves are not
sufficient. In addition, the design of local exhaust ventilation shall ensure that the
ventilation inlet point is as close as reasonably practicable to the actual welding
work; and
(v) refer to
ADOSH-SF – CoP 52.0 – Local Exhaust Ventilation.
3.3.4 Electricity and Radiation
(a) Employers shall ensure electrical and radiation hazards are eliminated or significantly
reduced through adherence to the following:
(i) all cord-connected electrical welding machines shall be tested in accordance with
the manufacturers specifications;
(ii) electrical welding machines shall only be connected to circuits protected by
residual current devices (RCDs) and shall be appropriately earthed; and
(iii) personnel performing welding activities shall ensure that electric cables are not
damaged by sparks, hot metal, etc.
3.3.5 Preventing Fire
(a) Employers shall ensure the following fire precautions are taken:
(i) move the work-piece to a safe location for carrying out the hot work process;
(ii) remove any combustible materials (such as flammable liquids, wood, paper,
textiles, packaging or plastics) from within 10 meters of the work;
(iii) ventilate spaces where vapors could accumulate, such as vehicle pits or trenches;
ADOSH-SF – Codes of Practice
CoP 28.0 - Hot Work Operations (e.g., Welding and Cutting)
Version 4.1 – 16h February 2026
Page 9 of 16
(iv) protect any combustible materials that cannot be moved, from close contact with
flame, heat, sparks or hot slag. Use appropriate guards or covers such as metal
sheeting, mineral fiber-boards or fire retardant blankets;
(v) check that there are no combustible materials hidden behind walls or partitions
which could be ignited, particularly if prolonged welding or cutting is planned;
(vi) use guards or covers to prevent hot particles passing through openings in floors
and walls (doorways, windows, etc);
(vii) maintain a continuous fire watch during the period of the work, and for at least an
hour afterwards; and
(viii) keep fire extinguishers nearby.
3.4 Hazardous Areas
(a) Employers shall ensure prior to the commencement of hot work in hazardous areas,
the following precautions are taken, to prevent any fire, explosion, injury or other
danger developing during the performance of the hot work:
(i) a “Hot-Work Permit” shall be obtained before any work is carried out in a
hazardous area where flammable or explosive gases and dusts may be present;
(ii) when the responsible person is satisfied that the hot work may safely proceed,
that person shall issue a “Hot-Work Permit”, in accordance with
ADOSH-SF – CoP
21.0 – Permit to Work Systems;
(iii) identify and control any fire hazard (including the presence of flammable or
combustible liquids, gases, vapors, dusts, fibers or substances) within 10 m from
the hot work;
(iv) ensure the appropriate ventilation of the hot-work area;
(v) appropriately locate the equipment, including emergency firefighting equipment;
(vi) isolate the area where the hot work is to be performed;
(vii) ensure the provision of a safe entry to and exit from the hot-work area;
(viii) the testing for the presence of any flammable gas or flammable vapor in the
atmosphere within the area and in any pipe, drum, tank, vessel and piece of
equipment adjacent to or involved in the hot work;
(ix) ensure the concentration of any flammable gas or flammable vapor, as
determined by the testing required is less than 5% of its Lower Explosion Limit
(LEL);
(x) if specified by the hot-work permit, a firewatcher shall be stationed in the area
near the hot work, for the safe conduct of the hot work and shall ensure that no
condition arises that will lead to a hazardous situation in the hot-work area;
(xi) the site or work area shall be secured overnight and at the expiry of a hot-
work permit period;
(xii) at the completion of a job, the equipment shall be returned to its normally secure
mode and the firefighting equipment that has been brought to the hot-work site
shall be returned to its normal storage; and
(xiii) at the completion of a job the “Hot-Work Permit” shall be signed off.
ADOSH-SF – Codes of Practice
CoP 28.0 - Hot Work Operations (e.g., Welding and Cutting)
Version 4.1 – 16h February 2026
Page 10 of 16
3.5 Electric Arc Welding
(a) Employers shall ensure the following:
(i) arc cutting and welding equipment is installed and used in accordance with the
manufacturers specifications;
(ii) the current used for electric arc welding is either direct or alternating but,
whichever system is used, the voltage be as low as is consistent with efficient
welding;
(iii) welding leads and welding return cables shall meet the following requirements:
1. insulation is appropriate for resisting hard usage;
2. are examined at least daily for defects;
3. for the part of the cable which is connected to the electrode holder it is as
flexible as reasonably practicable so as not to hamper the movement of the
welder; and
4. have the welding return section not less than that of the welding lead.
(iv) joints between cable sections are made with appropriately constructed insulated
cable couplings appropriately shrouded, so that live metal is not exposed if the
parts of the connector are separated;
(v) the welding return is firmly connected to the metal on which welding is taking
place, by means of a well-constructed clamp;
(vi) an electrode holder is fully insulated, so that the live portions cannot he touched
accidentally; and
(vii) when arc welding is suspended for a substantial period of time, such as during
lunch periods or overnight, the power source to the equipment is de-energized, the
electrodes are removed from the holders and the holders are placed so that
accidental contact or arcing cannot occur.
3.6 Gas Welding
(a) Employers shall ensure the following:
(i) under no circumstances any fittings on oxy-acetylene equipment be allowed to
be contaminated with grease or oil;
(ii) regulators are daily checked, at least daily; as they can fail in two ways - by the
increased forward flow of the controlled gas which is known as regulator creep
or by the reverse flow of another gas in the gas lines;
(iii) employees never use equipment fitted with a regulator in which a creep
condition is known to exist;
(iv) the use of the correct color and type of hoses and fittings recommended by the
manufacturers specifications;
(v) copper is never used on acetylene lines as substances are formed which may
spontaneously detonate;
(vi) flashback arresters are fitted to all oxy-acetylene equipment to overcome the
danger of flashback;
ADOSH-SF – Codes of Practice
CoP 28.0 - Hot Work Operations (e.g., Welding and Cutting)
Version 4.1 – 16h February 2026
Page 11 of 16
(vii) oxy-acetylene equipment is not left near hot equipment or metals which could
burn the leads; and
(viii) there is no smoking when welding or near welding activities.
3.7 Gas Cylinders
3.7.1 Storage of Gas Cylinders
(a) Employers shall ensure the following:
(i) all cylinders are stacked vertically, whether full or empty, and are secured against
falling;
(ii) full cylinders are kept separate from empty ones;
(iii) all cylinders are shielded from direct sunlight, or other heat, to avoid the buildup of
excess internal pressure which might lead to gas leakage or, in extreme cases,
bursting of the cylinder;
(iv) oxygen cylinders are stored at least 6 meters away from those containing
acetylene or LPG, since any mixture of oxygen with one of the fuel gases, which
can result from a leakage, could be highly explosive;
(v) oxygen cylinders are not kept in the same storeroom as LPG or acetylene cylinders;
and
(vi) refer to
ADOSH-SF – CoP 1.0 – Hazardous Substances and
ADOSH-SF – CoP 49.0 –
Compressed Gases and Air.
3.7.2 Cylinder Handling
(a) Employers shall ensure the following:
(i) employees hands and clothing are free from grit, grease and oil when cylinders
are handled to prevent them from slipping and to prevent grit from getting into
the valve, or grease on to the nozzle or valve;
(ii) nozzles are not used for handling purposes as they are not designed to take such
weight or stress;
(iii) cylinders in use are normally kept and moved in purpose built trolleys;
(iv) if it is necessary to move cylinders which are not in a trolley, regulators and hoses
are detached and a check made that valves are appropriately shut;
(v) under no circumstances cylinders are rolled along the ground;
(vi) if cylinders are to be lifted by crane, they are secured in a special carrier and on
no account are they to be lifted with chain or wire rope slings;
(vii) gas cylinders are treated with care and not subjected to shocks or falls;
(viii) when they are transported in a vehicle around a site, they are secured to prevent
injury in the event of any sudden vehicle movement, and when being unloaded
from a vehicle, they are not dropped to the ground;
(ix) acetylene cylinders are always transported and used in the vertical position. If
they have been subjected to the horizontal position (accidentally following a fall)
they shall be stood upright for 15 minutes to settle out before use; and
ADOSH-SF – Codes of Practice
CoP 28.0 - Hot Work Operations (e.g., Welding and Cutting)
Version 4.1 – 16h February 2026
Page 12 of 16
(x) Refer to
ADOSH-SF – CoP 1.0 – Hazardous Substances and
ADOSH-SF – CoP 49.0
– Compressed Gases and Air.
3.7.3 Cylinder Attachments
(a) Employers shall ensure the following:
(i) regulators are always fitted to the cylinders to reduce the gas pressure from that
in the cylinder to the working pressure of the blowpipe;
(ii) only regulators designed for the gas being used and rated for the current full
cylinder pressure are fitted to the cylinders;
(iii) the cylinder valve is "cracked open" before the regulator is fitted to the cylinder
to blow all the dust and other foreign matter clear;
(iv) the adjusting screw of the regulator is always released before the cylinder valve
is opened, and the cylinder valve is opened gradually;
(v) periodic checks are made to ensure that no gas is leaking from the regulator
when the pressure regulating screw is set at zero. Checks for gas leakage from
any part of the equipment shall only be made with water containing detergent.
Bubbles in the detergent indicate the presence of a leak;
(vi) hoses are:
1. kept for one type of gas only, and color coded for identification - red for
acetylene or other fuel gases (except LPG), orange for LPG and blue for
oxygen;
2. inspected daily before use to see that they are free from cuts, scratches,
cracks, burnt or worn patches; and
3. effectively clipped or crimped to the equipment and protected at all times
from sharp edges, falling metal, passing traffic and sparks from the welding
operation.
(vii) gas mixtures arising in use are prevented, e.g. if the blowpipe nozzle becomes
blocked, non-return valves (flashback arrestors) shall be fitted to each blowpipe
inlet connection;
(viii) in situations of high risk, flashback arrestors are fitted and examples of such
situations include:
1. in a confined space where access is difficult or the means of escape may be
endangered by fire/explosion;
2. operations under hot work permit adjacent to live operating plant;
3. near compressed air workings;
4. when employees are under training; and
5. where there is a device in the gas line with significant internal volume, eg.
a welding flux container.
(ix) blowpipes are dismantled and cleaned at regular intervals; and
(x) refer to
ADOSH-SF – CoP 49.0 – Compressed Gases and Air.
ADOSH-SF – Codes of Practice
CoP 28.0 - Hot Work Operations (e.g., Welding and Cutting)
Version 4.1 – 16h February 2026
Page 13 of 16
3.8 Inspection
(a) Employers shall ensure the following:
(i) visual checks are carried by users on welding and cutting equipment before use;
(ii) formal inspections are carried out by competent persons at regular intervals and in
accordance with the manufacturers' specification and at a minimum;
1. daily inspection and leak test all joints at working pressure;
2. weekly inspection (if in constant use) or before every use;
3. 6 monthly functional test by a competent person; and
4. 5 yearly (or as recommended by the manufacturer) refurbishment or
replacement. Elastomers and seals will wear and deteriorate in service and
deteriorate out of service. Items stored for one year or over without use
shall be inspected as per the annual maintenance inspection.
(iii) any welding and cutting equipment that is malfunctioning is immediately removed
from service.
ADOSH-SF – Codes of Practice
CoP 28.0 - Hot Work Operations (e.g., Welding and Cutting)
Version 4.1 – 16h February 2026
Page 14 of 16
4. Document Amendment Record
Version Revision Date Description of Amendment
Page/s Affected
4.0
15th July 2024
System acronym updated from OSHAD-SF
to ADOSH-SF to accurately reflect
document title
Throughout
Change from OSHAD to ADPHC
Change of Logo
Minor editorial changes throughout the
document without changing requirements.
Title of Mechanism 7.0 updated to ADOSH-
SF – Mechanism 7– Occupational Safety
and Health Practitioner and Service
Provider Registration
OSHAD-SF - Mechanism 8.0 - OSH
Practitioner Registration deleted
4.1
16th February
2026
Minor editorial changes throughout the
document without changing requirements
Throughout
ADOSH-SF – Codes of Practice
CoP 28.0 - Hot Work Operations (e.g., Welding and Cutting)
Version 4.1 – 16h February 2026
Page 15 of 16
نص غير رسمي مُستخرج من وثائق عامة؛ لا يُضمن التنسيق أو الاكتمال. يُرجى التحقق من المصدر الرسمي. في حال التعارض، يسود النص العربي. لا يُعد استشارة قانونية. المصدر الرسمي ↗