CoP 52.0 - Local Exhaust Ventilation
Abu Dhabi Occupational Safety and
Health System Framework
(ADOSH-SF)
Code of Practice
CoP 52.0 – Local Exhaust Ventilation
Version 4.1
February 2026
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 2 of 18
Table of Contents
1. Introduction ....................................................................................................................................................... 3
2. Training and Competency ............................................................................................................................. 4
3. Requirements .................................................................................................................................................... 5
3.1 Roles and Responsibilities ................................................................................................................. 5
3.2 Requirements of LEV Systems ........................................................................................................ 6
3.3 Paint Booths / Spray Finishing Booths ......................................................................................... 7
3.4 Chemical Fume Hoods / Laboratory Hoods ................................................................................. 8
3.5 Hoods and Enclosure Type Local Exhaust Ventilation Systems ....................................... 11
4. Record Keeping .............................................................................................................................................. 15
5. References ....................................................................................................................................................... 16
6. Document Amendment Record ................................................................................................................. 17
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 3 of 18
1. Introduction
(a) This Code of Practice (CoP) applies to all employers within the Emirate of Abu Dhabi.
This CoP is designed to incorporate requirements set by UAE and Abu Dhabi regulatory
authorities. If requirements of this document conflict with requirements set by
another regulatory authority, employers are required to follow the more stringent
requirement.
(b) This CoP sets requirements on how to control gas, vapour, dust, fume and mist in
workplace air using local exhaust ventilation (LEV) to extract contaminants before
they enter employee’s breathing zones.
(c) Definitions applicable to this CoP:
(i) Airborne contaminants: Particles, gases or vapours and combinations of these.
‘Particles’ include dusts, fumes, mists and fibres.
(ii) Air cleaner or arrestor: A device to remove contaminants from air (e.g. filters,
cyclone, sock, wet scrubber, electrostatic precipitator (EP)).
(iii) Air mover: Devices that move air- Fan, Turbo exhauster. The ‘engine’ that powers
the extraction system, usually a fan.
(iv) Breathing Zone: The region around operators from which they draw air for
breathing. Commonly defined as being within 300 mm of nose/mouth.
(v) Boundary layer: The stationary or turbulent layers of air near a surface which can
hold a contaminant cloud.
(vi) Inspirable dust: Any dust which can be inhaled.
(vii) Particulate-filter respirator: An air purifying respirator commonly referred to as a
dust or a fume respirator, which removes most of the dust or fume from the air
passing through the device.
(viii) Protective Coating: The application of a coating to protect metal surfaces from
corrosion, or to improve the appearance of a product.
(ix) Respirable dust: Is only that dust which is small enough to be inhaled into the
lungs. Airborne dust in sizes capable of passing through the upper respiratory
system to reach the lower lung passages.
(x) Receiving Hood: The entry point into the LEV that helps direct contaminants
away from the breathing zone of an employee.
(xi) Sash: A movable glass panel that covers the face area of a fume hood. Sashes
can be vertical, horizontal, or a combination of the two.
(xii) Working Zone: The location in the workplace where an activity is generating
contamination that could enter an employee’s breathing zone.
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 4 of 18
2. Training and Competency
(a) Employers shall ensure that OSH training complies with the requirements of:
(i)
ADOSH-SF – Element 5 – Training, Awareness and Competency.
(ii)
ADOSH-SF – Mechanism 7.0 – Occupational Safety and Health Practitioner and
Service Provider Registration.
(b) Employers shall ensure all relevant employees and contractors that perform tasks that
require LEV are trained on:
(i) hazards associated with the operations being completed that requires LEV;
(ii) design specification, capabilities and limitations of LEV used at their work site;
(iii) methods and procedures that will prevent contamination of clothing and
contamination of the employee’s breathing zone;
(iv) the importance of LEV as a control measures;
(v) safe work practices; and
(vi) operator maintenance requirements to ensure LEV is working appropriately.
(c) Employers shall ensure managers and supervisors of operations requiring LEV shall be
trained on:
(i) requirements listed in Section 2(b);
(ii) maintenance requirements to ensure LEV is working appropriately and within
specifications;
(iii) relevant design and installation principles for LEV systems to ensure that
provisions are fit for purpose;
(iv) how to recognize when LEV is not being used appropriately; and
(v) how to identify when the LEV is not working appropriately.
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 5 of 18
3. Requirements
3.1 Roles and Responsibilities
3.1.1 Employers
(a) Employers shall undertake their roles and responsibilities in accordance with the
general requirements of
ADOSH-SF – Element 1 – Roles, Responsibilities and Self-
Regulation Section 3.2.5.
(b) Employers shall ensure performing a risk assessment in accordance with
ADOSH-SF –
Element 2 – Risk Management to determine the risks associated to identify areas
where LEV is required to reduce employee’s exposures to hazards
materials/chemicals.
(c) Employers shall implement the Occupational Health and Safety hierarchy of controls
as defined in
ADOSH-SF – Element 2 – Risk Management, when developing control
measures to remove or reduce employee exposure to hazards.
(d) Employers shall ensure that LEV systems are designed and installed such that
identified hazards are managed and controlled to an acceptable level.
(e) Employers shall ensure that when LEV is not sufficient to achieve full compliance,
protective equipment or other control measures shall be used to keep the exposure of
employees to hazardous materials/chemicals within limits prescribed by applicable
local and federal regulations.
(f) Employers shall conduct air quality monitoring at regular intervals to provide on-going
assurance that LEV systems are working to an acceptable level.
(g) Employers shall develop a preventative maintenance plan to ensure LEV works
efficiently and according to manufacture specifications.
(h) Employers shall perform flow tests and inspect the LEV system on a regular basis (at
a minimum annually) and document the findings along with any maintenance
requirements.
(i) Employers shall ensure LEV are designed to the specification set by the American
Standards Institute:
ANSI/AIHA Z9.2-2006, Fundamentals Governing the Design and
Operation of Local Exhaust Ventilation System; or equivalent international standard.
(j) Employers shall ensure LEV are tested and inspected regularly (at a minimum annually)
to ensure the system work in accordance with manufactures specifications.
(k) Employers shall monitor the use of LEV to ensure employees are using LEV
appropriately.
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 6 of 18
3.1.2 Employees
(a) Employees shall undertake their roles and responsibilities in accordance with the
general requirements of
ADOSH-SF – Element 1 – Roles, Responsibilities and Self-
Regulation Section 3.2.7.
(b) Employees shall report any activity or defect relating to LEVs which they know is
reasonably practicable to endanger their safety or that of another person.
(c) Employees shall use appropriate work equipment or safety devices provided by the
employer in accordance with any training or instruction received in the use of the work
equipment or device concerned.
(d) Employees shall not perform any task requiring training until they have received the
required training.
(e) Employees shall not operate any piece of equipment that they are not familiar with,
competent to operate and/or appropriately trained on its use.
3.2 Requirements of LEV Systems
(a) LEV shall be designed to prevent dispersion into the air of dusts, fumes, mists, vapors
and gases in concentrations causing harmful exposure at any point of fallout.
(b) LEV shall be designed to ensure no dusts, fumes, mists, vapor or gases are drawn
through the work areas or walkways.
(c) Exhaust fans, jets, ducts, hoods, separators, and all necessary equipment, including
refuse receptacles, shall be designed, constructed, maintained and operated as to
ensure the required protection by maintaining volume and velocity of exhaust air
sufficient to gather dust, fumes, vapors or gases from equipment or processes.
(d) Air outlet from every LEV shall be discharged to the outside atmosphere. Systems
designed to collect non-hazardous materials (e.g. wood dust) can return air back into
the work area as long as it has a filtration system that removes repairable dusts and
particles and does not result in a harmful exposure to employees.
(e) Exhausts of LEV shall not be located in an area that will expose other employees or
near air intakes for building ventilation and/or climate control systems.
(f) The exhaust system shall be in operation continually during all operations which it is
designed to serve. If the employee remains in the contaminated zone, the system
shall continue to operate after the cessation of said operation, until the contaminants
are removed. Employees wearing respiratory protection shall not remove it until the
atmosphere is clear of contaminants.
(g) Exhausted material shall be subject to regular emissions monitoring where
appropriate, and as a minimum where exhaust material may be harmful to the
environment.
(h) LEV systems need to be designed for the material which they are intended to remove
from the work environment.
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 7 of 18
(i) When contaminants could create a combustible or explosive hazard, the LEV system
shall be designed to take this into account and reduce the potential for a fire or
explosion.
(j) LEVs shall have inspection or clean-out doors not to exceed 4 meters of running
length.
(k) A clean-out door shall be provided for servicing the fan and where necessary a drain
shall be provided.
(l) LEV ductwork shall be appropriately supported though its length to sustain its weight
plus any normal accumulation of contaminants in the interior during normal operating
conditions and any negative pressure exerted upon it.
(m) Joints and seams shall be sealed to prevent loss of contaminants during use and
prevent contamination of other work areas.
(n) Where ductwork passes through a combustible roof or wall, the roof or wall shall be
protected at the point of penetration by open space or fire-resistive material between
the duct and the roof or wall.
(o) Duct work shall not pass through firewalls unless no other practicable alternative is
available. An assessment shall be undertaken to identify the risks of the duct work
passing through the firewall to determine any compromise to the integrity of the
firewall.
(p) LEV systems shall be designed to produce as little noise as reasonably practicable.
(q) Makeup air in the work area shall be sufficient to prevent the creation of negative
pressure in the room that will reduce the effectiveness of the LEV.
(r) Where LEV systems require continuous positive pressure to be effective, appropriate
means of access and egress shall be provided, including where necessary air-lock
doors and / or operational access control.
3.3 Paint Booths / Spray Finishing Booths
(a) Booths shall provide a continuous, uniform and evenly distributed supply of air flow
throughout the spray painting area to the exhaust outlets. There shall be no pockets
of still air in the booth.
(b) The source of air supply shall be pulled from an area that is not contaminated with
hazardous substances or chemicals as to prevent excess accumulation of airborne
contaminants or unnecessary exposures to employees.
(c) Employees (e.g. spray painters) shall not be positioned between the spray gun and the
ventilation exhaust duct.
(d) Booths shall maintain an internal negative pressure during operation to prevent
leakage of contaminants into surrounding work areas.
(e) Booths shall be equipped with a negative pressure gauge and a gauge or alarm to
indicate if airflow drops below the minimum set air flow rate to capture contaminants.
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 8 of 18
(f) Booth ventilation system shall remain on for five (5) minutes after completing
spraying operations to purge the chamber.
(g) Booths shall provide a level of air velocity at any point within the booth that complies
with the following requirements:
(i) Minimum air velocity for downdraft booths and cross-draft booths where drafts
from outside the booth is equal to or less than 0.2 meters per second: 0.5 meters
per second;
(ii) Minimum air velocity for downdraft booths and cross-draft booths where drafts
from outside the booth is more than 0.2 meters per second: 0.8 meters per second;
and
(iii) Minimum air velocity for electrostatic spray painting and spray finishing without
operator: 0.4 meters per second.
(h) Refer to
ADOSH-SF – 48.0 – Spray Finishing for further requirements.
3.4 Chemical Fume Hoods / Laboratory Hoods
(a) Work Area (room) Design:
(i) work areas with chemical fume hoods or laboratory hoods shall be designed to have
no recirculation of air to the lab or any other spaces;
(ii) fume hoods and laboratory hoods shall be located so that person entering or
exiting the work area will not have to pass in front of the hood;
(iii) in rooms where there are fume hoods or laboratory hoods installed, there shall be
a minimum of two exits from the room. If this is not reasonably practicable, the
hood shall be located on the side of the room farthest from the door;
(iv) fume hoods and laboratory hoods shall not be directly opposite occupied work
stations;
(v) windows in laboratories containing fume hoods or laboratory hoods shall be fixed
closed; and
(vi) HVAC systems in laboratory areas shall be designed such that they automatically
close (or as a minimum, that dampers can be locally controlled) to avoid ingress of
toxic materials into heating, ventilation, and air conditioning systems.
(b) Supply Air:
(i) before a new fume hood or laboratory hood is put into operation, a survey shall be
conducted to ensure there is appropriate make-up air;
(ii) supply and exhaust volumes shall be such that the laboratory is under slightly
negative pressure, even when hoods are not operational, to prevent the escape of
contaminants;
(iii) ceiling and wall diffusers for the building ventilation system shall be directed so
that the incoming supply of air flow does not affect the air flow at the fume hood
or laboratory hood; and
(iv) supply air intake shall be a minimum of 15 meters from any fume hood or laboratory
hood exhaust.
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 9 of 18
(c) Variable Air Volume (VAV) Systems:
(i) VAV systems shall be designed by a competent engineer with experience in
designing VAV systems;
(ii) VAV systems shall maintain a minimum air velocity of 18 meters/min during periods
of non-use; and
(iii) Existing LEVs shall not be converted to VAV systems unless designed by a
competent engineer and tested to ensure it meets the minimum requirements for
capturing contaminants.
(d) Construction and Installation:
(i) chemical fume hoods and laboratory hoods shall maintain an average minimum
air velocity of 19 meters/min when in use. For VAV systems, the system shall
maintain this velocity when the sash is fully open;
(ii) a minimum of 9 measurements shall be taken in various locations of the working
area of the chemical fume hood or laboratory hood to ensure minimum average
air velocity is met. No result shall be less than 13.5 meters/min;
(iii) a competent person in the design of chemical fume hoods and laboratory hoods
shall determine the minimum number of air changes per hour required depending
on the use of the system. At a minimum, six air changes per hour will be required
for hazardous materials laboratories, but this can be increased depending on the
materials used in the laboratory;
(iv) chemical fume hoods and laboratory hoods and associated ductwork and fans
shall be constructed of a material compatible with the materials/contaminants
captured by the hood. All areas of potential leaks shall be sealed;
(v) portable, non-ducted fume hoods (e.g. use a filter to clean the air) are not
acceptable for use with hazardous chemicals;
(vi) all hoods shall have a working airflow indicator installed. Airflow indicators shall
be checked during regular maintenance of the hood to ensure it is working
appropriately and calibrated annually;
(vii) hood exhaust stacks shall extend at least two meters above the roof and one
meter above any parapet walls, whichever is greater;
(viii) hood exhausts shall be a minimum of 15 meters and preferable downwind from
any air intakes. This distance can be increased as needed to prevent re-
entrainment of exhaust fumes;
(ix) rain caps and other such devices are not allowed if they divert the exhaust
towards the roof;
(x) all plumbing utilities shall have shut-off valve or cock adjacent to the hood;
(xi) electrical outlets shall be outside the hood;
(xii) lighting fixtures shall be compatible with the contaminants captured by the
system. It is suggested to use fluorescent fixtures when feasible;
(xiii) lighting fixtures shall be sealed and vapour tight, UL-listed, and protected by a
transparent impact resistant shield; and
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 10 of 18
(xiv) sashes shall be made of safety glass. Polycarbonate sashes shall not be used for
chemical contaminants.
(e) Safe Work Practices:
(i) Employers shall ensure the following safe work practices are followed:
1. all work involving hazardous or odorous chemicals shall be performed in a
chemical fume hoods or laboratory hood;
2. all equipment and materials shall be placed at least 15 centimetres back
from the face of the hood and they shall not obstruct the movement of air
into the hood;
3. when sashes are used, they hall be kept as low as reasonably practicable
when the hood is in use;
4. employee’s heads shall not be placed into the hood when contaminants are
present;
5. hoods shall not be used as a storage area or overloaded with unnecessary
equipment and materials;
6. hoods shall not be used to for storage of hazardous chemical wastes;
7. foot traffic shall be minimized when the hood is in use;
8. the interior of the ventilation system shall be kept clean and tidy; and
9. no work shall be conducted in a malfunctioning hood.
(f) Test and Inspection:
(i) hoods shall have their performance tested and certified on an annual basis
(Emirates Authority for Standardization and Metrology approved third party entity);
(ii) hood testing shall be based on manufacture recommendations, applicable
international standards, and international best practices;
(iii) a competent person shall be responsible for performing the annual testing and
certification of hoods;
(iv) all identified deficiencies shall be reported and corrected. Hoods found unable to
provide appropriate airflow or leaking contaminants shall be taken out of service
until repairs are made;
(v) LEV systems shall undergo a daily visual pre-operation check and inspection; and
(vi) LEV systems shall undergo monthly inspection of air cleaning and filtration
components and maintenance as required.
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 11 of 18
3.5 Hoods and Enclosure Type Local Exhaust Ventilation Systems
(a) In addition to the requirements set in this CoP, the following operational specific
requirements for ventilation systems apply.
3.5.1 Hood and Enclosure Design
(a) All grinding and abrasive cutting-off wheel shall have manufacture supplied hoods in
place to protect the operator from the hazards of bursting wheels, as well as to provide
a means for the removal of dust and dirt generated. Equipment shall not be used
unless a hood is in place.
(b) Hoods shall be located as close as reasonably practicable to the operation.
(c) Exhaust hoods for floor stands, pedestals, and bench grinders shall be designed in
accordance with applicable standard requirements. The adjustable tongue shall be
kept in working order and shall be adjusted within one-quarter inch of the wheel
periphery at all times.
(d) Portable grinding operations, whenever the nature of the work permits, shall be
conducted within a partial enclosure. The opening in the enclosure shall be no larger
than is actually required in the operation and an average face air velocity of not less
than 200 cubic feet per minute shall be maintained.
(e) Hoods for polishing and buffing and scratch-brush wheels shall be constructed to
conform as closely to standard requirements as the nature of the work will permit.
(f) Cradle grinding and polishing operations shall be performed within a partial enclosure
meeting standard requirements. The operator shall be positioned outside the working
face of the opening of the enclosure. The face opening of the enclosure shall not be
any greater in area than that actually required for the performance of the operation
and the average air velocity into the working face of the enclosure shall not be less
than 150 feet per minute.
(g) Hoods for horizontal single-spindle disc grinders shall be constructed to conform as
closely as reasonably practicable to specifications of the grinder’s manufacturer. It is
essential that there be a space between the back of the wheel and the hood, and a
space around the periphery of the wheel of at least 25.4mm in order to permit the
suction to act around the wheel periphery. The opening on the side of the disc shall
be no larger than is required for the grinding operation, but shall never be less than
twice the area of the branch outlet.
(h) Horizontal double-spindle disc grinders shall have a hood encircling the wheels and
grinding chamber. The openings for passing the work into the grinding chamber shall
be kept as small as reasonably practicable, but shall never be less than twice the area
of the branch outlets.
(i) Vertical-spindle disc grinders shall be encircled with a hood so constructed that the
heavy dust is drawn off a surface of the disc and the lighter dust exhausted through
a continuous slot at the top of the hood.
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 12 of 18
(j) Grinding and polishing belt hoods shall be constructed as close to the operation as
reasonably practicable. The hood shall extend almost to the belt, and 1-inch wide
openings shall be provided on either side.
3.5.2 Enclosures
(a) Temporary enclosures shall be used when the object or structure is unable to be
transported. Any object measuring greater than 2.5m x 2.5m x 3.0m shall be
considered large in consideration with applicable local / national regulations or the
international standard. Temporary enclosures are also used for fixed structures, eg.
bridges or water tanks.
(b) Where monitoring indicates that persons in surrounding areas may be exposed to dust
levels in excess of the national exposure standards, they shall be excluded from the
area, where reasonably practicable, by warning signs and barricading, or provided with
personal protective equipment (PPE).
(c) Grinding Wheels: Ventilation systems for grinding wheels on floor stands, pedestals,
benches, and special-purpose grinding machines and abrasive cutting-off wheels shall
have not less than the minimum exhaust volumes shown in Table 1, with a
recommended minimum duct velocity of 4,500 feet per minute in the branch and
3,500 feet per minute in the main. The entry losses from all hoods except the vertical-
spindle disc grinder hood shall equal 0.65 velocity pressure for a straight take-off and
0.45 velocity pressure for a tapered take-off.
Wheel diameter(inches) Wheel width (inches) Minimum exhaust volume
(feet3/min)
To 9 1 1/2 220
Over 9 to 16 2 390
Over 16 to 19 3 500
Over 19 to 24 4 610
Over 24 to 30 5 880
Over 30 to 36 6 1,200
Table 1 - Grinding and Abrasive Cutting-Off Wheels
Note: For any wheel wider than wheel diameters shown in the above table, increase the exhaust volume
by the ratio of the new width to the width shown.
Example:
If wheel width = 4 1/2 inches, then 4.5 divided by 4 X 610 = 686 (rounded to 690).
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 13 of 18
(d) Scratch-brush, buffing, and polishing wheels: Scratch-brush wheels and all buffing and
polishing wheels mounted on floor stands, pedestals, benches, or special-purpose
machines shall have not less than the minimum exhaust volume shown in below Table
2.
Wheel diameter(inches) Wheel width (inches) Minimum exhaust volume
(feet3/min)
To 9 2 300
Over 9 to 16 3 500
Over 16 to 19 4 610
Over 19 to 24 5 740
Over 24 to 30 6 1040
Over 30 to 36 6 1,200
Table 2 - Buffing and Polishing Wheels
(e) Grinding wheels/discs for horizontal single-spindle disc grinders: Grinding wheels or
discs for horizontal single-spindle disc grinders shall be hooded to collect the dust or
dirt generated by the grinding operation and the hoods shall be connected to branch
pipes having exhaust volumes as shown in Table 3.
Disc diameter(inches) Minimum exhaust volume
(feet3/min)
Up to 12 220
Over 12 to 19 390
Over 19 to 30 610
Over 30 to 36 880
Table 3 - Horizontal Single-Spindle Disc Grinder
(f) Grinding wheels/discs for horizontal double-spindle disc grinders: Grinding wheels or
discs for horizontal double-spindle disc grinders shall have a hood enclosing the
grinding chamber and the hood shall be connected to one or more branch pipes having
exhaust volumes as shown in Table-4.
Disc diameter(inches) Minimum exhaust volume (feet3/min)
Up to 19 610
Over 19 to 25 880
Over 25 to 30 1200
Over 30 to 53 1770
Over 53 to 72 6280
Table 4 - Horizontal Double-Spindle Disc Grinder
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 14 of 18
(g) Grinding wheels/discs for vertical single-spindle disc grinders: Grinding wheels or
discs for vertical single-spindle disc grinders shall be encircled with hoods to remove
the dust generated in the operation. The hoods shall be connected to one or more
branch pipes having exhaust volumes as shown in Table 5.
Disc
diameter(inches)
One-half or more of disc covered Disc not covered
Number (1) Exhaust foot
(3)/min Number (1) Exhaust
foot3/min
Up to 20 1 500 2 780
Over 20 to 30 2 780 2 1,480
Over 30 to 53 2 1,770 4 3,530
Over 53 to 72 2 3,140 5 6,010
Table 5 - Vertical Spindle Disc Grinder
(1)
Number of exhaust outlets around periphery of hood, or equal distribution provided by other means.
(h) Grinding and Polishing Belts: Grinding and polishing belts shall be provided with hoods
to remove dust and dirt generated in the operations and the hoods shall be connected
to branch pipes having exhaust volumes as shown in Table 6.
Belts width (inches) Exhaust volume (feet 3/min)
Up to 3 220
Over 3 to 5 300
Over 5 to 7 390
Over 7 to 9 500
Over 9 to 11 610
Over 11 to 13 740
Table 6- Grinding and Polishing Belts
(i) Cradle and swing-frame grinders. Where cradles are used for handling the parts to be
ground, polished, or buffed, requiring large partial enclosures to house the complete
operation, a minimum average air velocity of 150 feet per minute shall be maintained
over the entire opening of the enclosure. Swing-frame grinders shall also be
exhausted in the same manner as provided for cradles.
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 15 of 18
4. Record Keeping
(a) Employers shall ensure they keep appropriate records as required by their OSHMS
including, but not limited to valid and up to date test and inspection certificates for
LEV systems. These shall be maintained on site for the lifetime of the LEV system.
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 16 of 18
5. References
•
Controlling Airborne Contaminants at Work-UK HSE Book HSG 258
•
ESMA Standard 209 E: Industrial Safety And Health Regulations – Part 3:
Occupational Health And Environmental Control
•
American National Standards Institute: ANSI/AIHA Z9.2-2006, Fundamentals
Governing the Design and Operation of Local Exhaust Ventilation System
•
OSHA PART 1910 – Occupational Safety and Health Standards — Subpart G—
Occupational Health and Environmental Control § 1910.94 Ventilation
•
OSHA PART 1926.57: Ventilation
•
OSHA Technical Manual Section III- Chapter 3 (Ventilation Investigation)
•
OSHA Standard on Respiratory Protection - 29 CFR 1910.134
•
Industrial Sector OSH Regulatory Authority, Industrial Development Bureau (IDB)
Awareness Flyer on Abrasive Blasting & Spray Painting
•
U.K HSE INDG408 Clearing the Air- A simple guide to buying and using Local
Exhaust Ventilation (LEV)
ADOSH-SF – Codes of Practice
CoP 52.0 – Local Exhaust Ventilation - Version 4.1 – 16th February 2026 Page 17 of 18
6. Document Amendment Record
Version Revision Date Description of Amendment
Page/s Affected
4.0
15th July 2024
System acronym updated from OSHAD-SF
to ADOSH-SF to accurately reflect
document title
Throughout
Change from OSHAD to ADPHC
Change of Logo
Minor editorial changes throughout the
document without changing requirements.
Title of Mechanism 7.0 updated to ADOSH-
SF – Mechanism 7– Occupational Safety
and Health Practitioner and Service
Provider Registration
OSHAD-SF - Mechanism 8.0 - OSH
Practitioner Registration deleted
4.1
16th February
2026
Minor editorial changes throughout the
document without changing requirements
Throughout